AEMC ML912 AC Current Logger is a two channel AC current recording device powered by two alkaline batteries. This AC current logger incorporates two user selectable measurement ranges of 0 to 100 Amps and 0 to 1000 Amps.
- 64 samples per cycle
- Programmable storage rates from 8 every second to 1 every day
- 3 user selectable storage modes
- Stores up to 240,000 measurements in non-volatile memory
- Powered by standard Alkaline batteries
- Lightweight, compact, fits anywhere
- 5 LED indicators quickly and clearly display logger status
- Includes DataView software for data storage, real-time waveform display, analysis and report generation
- Isolated USB communication
- 600V CAT III; 300V CAT IV
- USB cable, DataView CD-ROM, 2x1.5V AA-cell alkaline batteries, user manual and warranty card.
ELECTRICAL: | |
Channels | Two |
Input | Captive MiniFlex AC Current Flexible Sensors |
Range | 0.5 to 100AAC 5 to 1000AAC |
Accuracy (50/60Hz) | 0 to 1A unspecified 1 to 100A: ±(1% of Reading + 0.5A) 0 to 5A unspecified 5 to 1000A: ±(1% of Reading + 1A) |
Resolution | 0.1A |
Sample Rate | 64 samples/cycle |
Storage Rate | Programmable from 125ms to 1 day |
Storage Technique | Start/Stop, FIFO and Extended Recording Mode (XRM) |
Recording Length | 15 minutes to 8 weeks, programmable using DataView |
Memory | 240,000 measurements (512kB). Recorded data is stored in non-volatile memory and retained even if battery is low or removed. |
Communication | USB 2.0 optically isolated |
Power Source | 2x1.5V AA-cell alkaline batteries |
Battery Life | 100 hrs to >45 days (dependent on storage rate/recording length) |
ENVIRONMENTAL: | |
Operating Temp. | 14° to 122°F (-10° to 50°C) |
Storage Temp. | -4° to 140°F (-20° to 60°C) |
Relative Humidity | Up to 85% at 95°F (35°C), Non-condensing |
Altitude | 2000m |
SAFETY & ELECTRO-MAGNETIC COMPATIBILITY: | |
Safety Rating | EN61010-1; 600V CAT III; 300V CAT IV; Pollution Degree 2 |
Protection Degree | IP40 |
Electro-Magnetic Compatibility | EN 61326-1; 07/1997 (+A1 10/1998, +A2 09/2001, +A3 05/2004) |
MECHANICAL: | |
Sensor/Cable Length | Sensor: 6" (152mm) / Cable: 6 ft (2m) |
Case | UL94-V0 |
Vibration | IEC 68-2-6 (1.5mm, 10 to 55Hz) |
Shock | IEC 68-2-27 (30G) |
Drop | IEC 68-2-32 (1m) |
Dimensions | 4.95 x 2.75 x 1.28" (136 x 70 x 32mm) w/o Sensor |
Weight | 8.67 oz (245g) with battery |
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Split phase load monitoring | |
Neutral and ground current monitoring | |
Intermittent problem detection | |
Harmonic current monitoring using DataView software | |
Machine load monitoring |