Fluke 1587 Insulation Multimeter (Mfg Part No. 2157271) combines a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit. This insulation multimeter provides maximum versatility for both troubleshooting and preventative maintenance.
- Auto discharge of capacitive voltage
- AC/DC Voltage
- DC millivolts
- AC/DC milliamps
- Continuity
- Remote probe, test leads, alligator clips
- Rugged, utility hard case
- Auto power off to save battery power
- True-rms
- Large display with backlight
- Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
- CAT III 100V, CAT IV 600V measurement category
- Accepts optional Fluke TPAKTM magnetic hanging system to free your hands for other work
- Three-year warranty
- Insulation test smoothing reading
- Frequency
- Capacitance
- Diode test
- Temperature
- Min/Max
- Low pass filter (for work on VSD's)
- K-type thermocouple
Operating temperature | –20 °C to +55 °C |
Storage temperature | -40°C to +60°C |
Humidity (Without Condensation) | 0% - 95% (10 °C – 30 °C) 0% - 75% (30 °C – 40 °C) 0% - 40% (40 °C – 55 °C) |
Operating Altitude | Operating Altitude 2000 m |
Overvoltage category | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V |
Agency Approvals | 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V |
Size | 203 x 100 x 50 mm (with holster) |
Weight | 624 g |
Battery life Alkaline | Meter use: 1000 hours Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. |
IP Rating | IP40 |
Voltage DC: | Maximum Voltage: 1000 V |
Accuracy: ±(0.09%+2) | |
Maximum Resolution: 0.001V | |
Voltage AC: | Maximum Voltage: 1000 V |
Accuracy: ±(2%+3) | |
AC Bandwidth: 5kHz* *with low pass filter; 3db @ 800 Hz | |
Maximum Resolution: 0.1 mV | |
Current DC: | Maximum Amps: 400mA |
Amps Accuracy: ±(0.2%+2) | |
Maximum Resolution: 0.01 mA | |
Current AC: | Maximum Amps: 400mA |
Amps Accuracy: ±(1.5%+2)* *1kHz bandwidth | |
Maximum Resolution 0.01 mA | |
Resistance: | Maximum Resistance: 50 MΩ |
Accuracy ±(0.9%+2) | |
Maximum Resolution: 0.1Ω | |
Capacitance: | Maximum Capacitance: 9,999 µF |
Accuracy: ±(1.2%+2) | |
Maximum Resolution: 1 nF | |
Frequency: | Maximum Frequency: 100 kHz |
Accuracy: ±(0.1%+1) | |
Maximum Resolution: 0.01 Hz | |
Temperature Measurement: | 40.0 °C to 537 °C -40.0 °F to 998 °F excluding probe |
Diode Test: | Range: 6 V |
Resolution: 1 mV | |
Accuracy: ±(2% + 1) | |
Insulation Test: | |
Minimum Test Current @ 1kΩ/V: | 1mA |
Maximum Resistance per Test Voltage: | 1000V: 2 GΩ |
Maximum Resolution per Test Voltage: | 50V: 0.01 MΩ 100V: 0.01 MΩ 250V: 0.1 MΩ 500V: 0.1 MΩ 1000V: 0.1 MΩ |
Accuracy per Test Voltage: | 50V: ±(3 % + 5) 100V: ±(3 % + 5) 250V: ±(1.5 % + 5) 500V: ±(1.5 % + 5) 1000V: ±(1.5 % + 5) to 600 MΩ, ±(10 % + 3) above 600 MΩ |
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.