Revenue grade multi-functional power and energy meter meets ANSI C12.2 billing grade accuracy and is the ideal choice for the monitoring and controlling of power distribution systems. Features data logging capabilities, True-RMS parameter measurement, digital RS485 communication port, and is compatible with different current transformers. DIN-rail mount transducer without LCD display, 1A input, and and 20 to 60 VDC power supply.
Revenue grade multi-functional power and energy meter meets ANSI C12.2 billing grade accuracy and is the ideal choice for the monitoring and controlling of power distribution systems. Features data logging capabilities, True-RMS parameter measurement, digital RS485 communication port, and is compatible with different current transformers. DIN-rail mount transducer without LCD display, 1A input, and and 20 to 60 VDC power supply.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
| Accuracy Acuvim-II | Accuracy Acuvim-IIR/IIE/IIW | Resolution | Range | |
| Voltage | 0.2% | 0.2% | 0.1V | 20V~1000kV |
| Current | 0.2% | 0.2% | 0.1mA | 5mA~50000A |
| Power | 0.5% | 0.2% | 1W | -9999MW~9999MW |
| Reactive Power | 0.5% | 0.2% | 1var | 9999Mvar~9999Mvar |
| Apparent Power | 0.5% | 0.2% | 1VA | 0~9999MVA |
| Power Demand | 0.5% | 0.2% | 1W | -9999MW~9999MW |
| Reactive Power Demand | 0.5% | 0.2% | 1var | -9999Mvar~9999Mvar |
| Apparent Power Demand | 0.5% | 0.2% | 0.2% | 0~9999MVA |
| Power Factor | 0.5% | 0.2% | 0.001 | -1.000~1.000 |
| Frequency | 0.2% | 0.2% | 0.01Hz | 45.00~65.00Hz |
| Energy Primary | 0.5% | 0.2% | 0.1kWh | 0-99999999.9kWh |
| Energy Secondary | 0.5% | 0.2% | 0.001kWh | 0-999999.999kWh |
| Reactive Energy Primary | 0.5% | 0.2% | 0.1kvarh | 0-99999999.9kvarh |
| Reactive Energy Secondary | 0.5% | 0.2% | 0.001kvarh | 0-999999.999kvarh |
| Apparent Energy Primary | 0.5% | 0.2% | 0.1kVAh | 0-99999999.9kVAh |
| Apparent Energy Secondary | 0.5% | 0.2% | 0.001kVAh | 0-999999.999kVAh |
| Harmonics | 1.0% | 1.0% | 0.1% | 0.0%~100.0% 20.0%~100.0% (IIR/IIE/IIW) |
| Phase Angle | 2.0% | 2.0% | 0.1° | 0.0°~359.9° |
| Unbalance Factor | 2.0% | 2.0% | 0.1% | 0.0%~100.0% |
| Running Time | 0.01h | 0~9999999.99h |
| Current Inputs (Each Channel) | ||||
| Nominal Current | 5A /1A | |||
| Metering Range | 0~10A AC | |||
| Withstand | 20Arms continuous, 100Arms for 1 second, non-recurring | |||
| Burden | 0.05VA (typical) @ 5Arms | |||
| Pickup Current | 0.1% of nominal | |||
| Accuracy | 0.2% full scale | |||
| Voltage Inputs (Each Channel) | ||||
| Nominal Full Scale | 400V AC L-N, 690V AC L-L (+20%) | |||
| Withstand | 1500V AC continuous 2500V AC, 50/60Hz for 1 minute | |||
| Input Impedance | 2Mohm per phase | |||
| Metering Frequency | 45Hz~65Hz | |||
| Pickup Voltage | 10V AC (30V AC for Acuvim IIR/IIE/IIW) | |||
| Accuracy | 0.2% full scale | |||
| Energy Accuracy (Acuvim IIR/IIE/IIW) | ||||
| Active | According to IEC 62053-22: Class 0.2s According to ANSI C12.20: Class 0.2s | |||
| Reactive (according to IEC 62053-23) | Class 2 | |||
| Harmonic Resolution | ||||
| Metered Value | Acuvim II: 31st harmonic Acuvim IIR/IIE/IIW: 63rd harmonic | |||
| Control Power | ||||
| Universal | AC or DC | |||
| Operating Range | 100~415V AC, 50/60Hz 100~300V DC | |||
| Burden | 5W | |||
| Frequency | 50/60Hz | |||
| Withstand | 3250V AC, 50/60Hz for 1 minute Installation Category III (Distribution) | |||
| Low Voltage DC Control Power (Optional) | ||||
| Operating Range | 20~60V DC | |||
| Burden | 5W | |||
Click on a category to view a selection of compatible accessories with the Accuenergy Acuvim IIR-M-1A-P2 Intelligent DIN Power Meter/Data Logger, 1 A input, 20-60 Vdc.
Click on a category to view a selection of compatible accessories with the Accuenergy Acuvim IIR-M-1A-P2 Intelligent DIN Power Meter/Data Logger, 1 A input, 20-60 Vdc.