This direct reading tester measures from 10MΩ to 1999Ω, and is auto-ranging, so it automatically seeks out the optimum measurement range. This kit includes a ground resistance tester with two 150ft color-coded leads on spools, one 30ft lead, two 14.5" T-shaped auxiliary ground electrodes, one set of five spaded lugs, 100ft tape measurer, and a carrying bag.
This direct reading tester measures from 10MΩ to 1999Ω, and is auto-ranging, so it automatically seeks out the optimum measurement range. This kit includes a ground resistance tester with two 150ft color-coded leads on spools, one 30ft lead, two 14.5" T-shaped auxiliary ground electrodes, one set of five spaded lugs, 100ft tape measurer, and a carrying bag.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
The AEMC 3640 Digital Ground Resistance Tester performs ground resistance measurement. Easy to use - simply connect the leads, press to measure, and read. The large LCD (nearly 3/4" high) also indicates low battery status, overrange, and lead reversals.
The 3640 comes with 3 color coded terminals to aid in easy hookup. Three LED indicators on the front panel continuously warn the user of measurement problems to ensure accurate and reliable tests.
Features
Applications
| Range | 0.00 to 19.99Ω 20.00 to 199.9Ω 200.0 to 1999Ω |
| Measurement Range | 20Ω 200Ω 2000Ω |
| Resolution | 10mΩ 100mΩ 1Ω |
| Test Current | 10mA 1mA 0.1mA |
| Accuracy in % of Reading | 2% Reading ±1 ct 3% Reading ±3 cts |
| Accuracy Reference Conditions | 23°C ±3K, 50% RH ±10%, battery at 8V ±0.2V, external magnetic field |
| Resistance Measurement Frequency | 128Hz square wave |
Click on a category to view a selection of compatible accessories with the AEMC 3640 Ground Resistance Tester Kit, 3-Point, 150 ft.
| Range | 0.00 to 19.99Ω 20.00 to 199.9Ω 200.0 to 1999Ω |
| Measurement Range | 20Ω 200Ω 2000Ω |
| Resolution | 10mΩ 100mΩ 1Ω |
| Test Current | 10mA 1mA 0.1mA |
| Accuracy in % of Reading | 2% Reading ±1 ct 3% Reading ±3 cts |
| Accuracy Reference Conditions | 23°C ±3K, 50% RH ±10%, battery at 8V ±0.2V, external magnetic field |
| Resistance Measurement Frequency | 128Hz square wave |
Click on a category to view a selection of compatible accessories with the AEMC 3640 Ground Resistance Tester Kit, 3-Point, 150 ft.