Dwyer 616D-20B PRESSURE TRANSMITTER, DIN RAIL, 10/0/10
- Mounting style allows for several units to be mounted closely together reducing required space.
- A wide range of models are available factory calibrated to specific ranges.
- The span and zero controls are for use when checking calibration.
They are not intended for re-ranging to a significantly different span. - Versatile circuit design enables operation in 2-wire current loops.
Specifications:
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: ±0.25% F.S.
at 70°F.
Stability: ±1% F.S./yr.
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Pressure Limits: 11 psig.
Thermal Effect: ±0.02% F.S./°F (0.0012% F.S./°C).
Power Requirements: 10-35 VDC (2-wire).
Output Signal: 4 to 20 mA.
Zero and Span Adjustments: Potentiometers for zero and span.
Loop Resistance: DC: 0-1250 ohms maximum.
Current Consumption: DC: 38 mA maximum.
Electrical Connections: Screw-type terminal block.
Process Connections: 1/8" female NPT.
Accessories included are two barbed fittings for 1/8" (3.12 mm) and 3/16" (4.77 mm) I.D.
rubber or vinyl tubing.
Mounting Orientation: Vertical, on a 1.378" (35 mm) DIN rail.
Weight: 4.8 oz (136 g).