Image is for reference only, refer to product info for complete details.
Designed for low differential pressure applications that require stringent pressure monitoring and alarming and have a complete system with a fixed segment LCD which enables access to pressure, security, calibration, and alarm set-up with a range of 0 to 0.5" wc.
Designed for low differential pressure applications that require stringent pressure monitoring and alarming and have a complete system with a fixed segment LCD which enables access to pressure, security, calibration, and alarm set-up with a range of 0 to 0.5" wc.
Discontinued!
This product has been discontinued and is no longer available.
There is no direct replacement, however we recommend the:
Not what you're looking for? Let’s do a search and help you find what you need.
The room pressure monitor stores peak and valley process readings.
Features
Applications
Service | Air and non-combustible, compatible gases |
Wetted Materials | Consult factory |
Housing Material | Die cast aluminum case and SS bezel |
Accuracy | ±0.5% RSS (includes non-linearity: ±0.49%, hysteresis: ±0.05% and non-repeatability: ±0.05%), or ±1% RSS (includes non-linearity: ±0.99%, hysteresis: ±0.05% and non-repeatability: ±0.05%) |
Pressure Limits | Ranges 0.5 and 1.0 in w.c: 9 psi; Ranges 2.5 and 5 in w.c. : 1.5 psi |
Temperature Limits | 32 to 140°F (0 to 60°C) |
Compensated Temperature Limits | 32 to 140°F (0 to 60°C) |
Thermal Effects | 0.02%/°F (0.036%/°C) from 77°F (25°C) |
Power Requirements | 12-28 VDC, 12-28 VAC 50 to 400 Hz |
Power Consumption | 3 VA max |
Output Signal | 4-20 mA DC into 900 Ω max |
Zero and Span Adjustments | Accessible via menus |
Response Time | 8 ms |
Display | Backlit 4 digit LCD 0.4" height LED indicators for set point and alarm status |
Electrical Connections | 15 pin male high density D-sub connection. 18" (46 cm) cable with 10 conductors included |
Process Connections | ⅛" female NPT. Side or back connections |
Mounting Orientation | Mount unit in vertical plane. Size: 4.75" (120.7 mm) OD x 2-21/32 (67.5 mm) |
Weight | 1.75 lb (794 g) |
Service | Air and non-combustible, compatible gases |
Wetted Materials | Consult factory |
Housing Material | Die cast aluminum case and SS bezel |
Accuracy | ±0.5% RSS (includes non-linearity: ±0.49%, hysteresis: ±0.05% and non-repeatability: ±0.05%), or ±1% RSS (includes non-linearity: ±0.99%, hysteresis: ±0.05% and non-repeatability: ±0.05%) |
Pressure Limits | Ranges 0.5 and 1.0 in w.c: 9 psi; Ranges 2.5 and 5 in w.c. : 1.5 psi |
Temperature Limits | 32 to 140°F (0 to 60°C) |
Compensated Temperature Limits | 32 to 140°F (0 to 60°C) |
Thermal Effects | 0.02%/°F (0.036%/°C) from 77°F (25°C) |
Power Requirements | 12-28 VDC, 12-28 VAC 50 to 400 Hz |
Power Consumption | 3 VA max |
Output Signal | 4-20 mA DC into 900 Ω max |
Zero and Span Adjustments | Accessible via menus |
Response Time | 8 ms |
Display | Backlit 4 digit LCD 0.4" height LED indicators for set point and alarm status |
Electrical Connections | 15 pin male high density D-sub connection. 18" (46 cm) cable with 10 conductors included |
Process Connections | ⅛" female NPT. Side or back connections |
Mounting Orientation | Mount unit in vertical plane. Size: 4.75" (120.7 mm) OD x 2-21/32 (67.5 mm) |
Weight | 1.75 lb (794 g) |