A 19" modular 1U expansion shelf for use with the C3MK Power System, which can be configured with up to four 96% efficient rectifiers (maximum 223 A). With the addition of the power system, it has the flexibility to be configured up to 3500 A.
A 19" modular 1U expansion shelf for use with the C3MK Power System, which can be configured with up to four 96% efficient rectifiers (maximum 223 A). With the addition of the power system, it has the flexibility to be configured up to 3500 A.
Discontinued!
This product has been discontinued and is no longer available. There are no replacement options.
We can help you find what you need:
| Input | |
| Voltage | 1P3W 240 VAC (nominal 176 to 275 VAC) 3 Ø 4 W 380 VAC |
| Frequency | 45 to 66 Hz |
| Protection | Under and over voltage |
| Efficiency | 96% maximum (3 kW module) 96% typical (2 kW module) |
| Output | |
| Output | Voltage: DEFAULT -54 VDC Current: 222 A maximumimum (3 kW 4 modules) |
| Adjustment Range | -42 to 58 VDC |
| Regulation | Line: ±0.5% maximum Load: ±1.0% maximum Temperature: ±0.5% maximum |
| Noise | ≤250 mVp-p (2 kW 3 modules) ≤300 mVp-p (3 kW 3 modules) |
| Setpoint Accuracy | ±0.5% |
| Over Current | 101 to 110% |
| Protection | -59 VDC over (recycle input to reset), thermal shutdown |
| General Specifications | |
| Temperature | Operating: -40 to 167°F (-40 to 75°C) (Derating above 3 kW: 113°F [45°C] / 2 kW: 131°F [55°C]) Storage: -40 to 176°F (-40 to 80°C) |
| Humidity | Operating: 10 to 95% (non-condensing) Storage: 5 to 95% (non-condensing) |
| Cooling | Fan cooling |
| Altitude | 6566' (2000 m) |
| Dimensions | 19 x 16.42 x 1.75" (465 x 417 x 44.4 mm) |