A 19" modular, configurable, and highly efficient 1U 48 VDC power system with up to three 96% efficient rectifiers (maximum 167 A). Featuring the addition of the 1U Cambia expansion shelf, the system has the flexibility to be configured up to 3500 A.
A 19" modular, configurable, and highly efficient 1U 48 VDC power system with up to three 96% efficient rectifiers (maximum 167 A). Featuring the addition of the 1U Cambia expansion shelf, the system has the flexibility to be configured up to 3500 A.
Discontinued!
This product has been discontinued and is no longer available. There are no replacement options.
We can help you find what you need:
Features
Applications
| Input | |
| Voltage | 1 Ø 3 W 240 VAC (nominal 176 to 275 VAC) 3 Ø 4 W 380 VAC |
| Frequency | 45 to 66 Hz |
| Protection | Under and over voltage |
| Efficiency | 96% maximum (3 kW module) 96% typical (2 kW module) |
| Output | |
| Output | Voltage: Default -54 VDC Current: 166.5 A maximum (3 kW 3 modules) |
| Adjustment Range | -42 to 58 VDC |
| Regulation | Line: ±0.5% maximum Load: ±1.0% maximum Temperature: ±0.5% maximum |
| Noise | ≤250 mVp-p (2 kW 3 modules) ≤300 mVp-p (3 kW 3 modules) |
| Setpoint Accuracy | ±0.5% |
| Over Current | 101 to 110% |
| Protection | -59 VDC over (recycle input to reset), thermal shutdown |
| General Specifications | |
| Operating Temperature | -40 to 167°F (-40 to 75°C) Derating above 3 kW: 113°F (45°C) / 2 kW: 131°F (55°C) |
| Storage Temperature | -40 to 176°F (-40 to 80°C) |
| Humidity | Operating: 10 to 95% (non-condensing) Storage: 5 to 95% (non-condensing) |
| Cooling | Fan cooling |
| Altitude | 6566' (2000 m) |
| Dimensions | 18.31 x 16.42 x 1.75" (465 x 417 x 44.4 mm) |
| Input | |
| Voltage | 1 Ø 3 W 240 VAC (nominal 176 to 275 VAC) 3 Ø 4 W 380 VAC |
| Frequency | 45 to 66 Hz |
| Protection | Under and over voltage |
| Efficiency | 96% maximum (3 kW module) 96% typical (2 kW module) |
| Output | |
| Output | Voltage: Default -54 VDC Current: 166.5 A maximum (3 kW 3 modules) |
| Adjustment Range | -42 to 58 VDC |
| Regulation | Line: ±0.5% maximum Load: ±1.0% maximum Temperature: ±0.5% maximum |
| Noise | ≤250 mVp-p (2 kW 3 modules) ≤300 mVp-p (3 kW 3 modules) |
| Setpoint Accuracy | ±0.5% |
| Over Current | 101 to 110% |
| Protection | -59 VDC over (recycle input to reset), thermal shutdown |
| General Specifications | |
| Operating Temperature | -40 to 167°F (-40 to 75°C) Derating above 3 kW: 113°F (45°C) / 2 kW: 131°F (55°C) |
| Storage Temperature | -40 to 176°F (-40 to 80°C) |
| Humidity | Operating: 10 to 95% (non-condensing) Storage: 5 to 95% (non-condensing) |
| Cooling | Fan cooling |
| Altitude | 6566' (2000 m) |
| Dimensions | 18.31 x 16.42 x 1.75" (465 x 417 x 44.4 mm) |