Streamline UPS and lead-acid battery diagnostics with this battery tester pro kit. Designed to measure and record guidance, this kit includes an L-shaped pin-type lead, which lets you reach deep into the battery racks and probe the entire terminals.
Streamline UPS and lead-acid battery diagnostics with this battery tester pro kit. Designed to measure and record guidance, this kit includes an L-shaped pin-type lead, which lets you reach deep into the battery racks and probe the entire terminals.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
Compatible with many battery types, including lead-acid, nickel-cadmium and nickel-hydride batteries. Plus, it comes with a carrying case for easy transportation to and from work sites.
Features
The battery tester sets a new standard for UPS and lead-acid battery diagnostics. Since the battery’s internal resistance and voltage are measured using the impedance method, diagnostics can be performed while the battery is connected to its host device, without taking it offline. Proprietary noise reduction technology allows more accurate measurement, even in noisy environments.
By using its comparator function to simultaneously measure the internal resistance and voltage of a lead-acid, nickel-cadmium, or nickel-hydride battery, the battery tester can generate comparative judgments quantifying degradation of the cell based on user-specified threshold values. Furthermore, voltage sign detection facilitates instantaneous determination of whether batteries have been connected properly in newly installed UPS systems.
The battery tester's auto-hold function automatically holds measured values once they stabilize. The instrument’s auto-memory function, which automatically stores measured values resulting from the auto-hold function in its internal memory, further streamlines work tasks.
The pin-type lead with L-shaped tips significantly improves ease of use when inspecting batteries installed in confined locations.
If you’re measuring a number of batteries in a large area, use the included shoulder strap to carry the instrument with you while making measurements. Or if there are numerous batteries at a single location, use the magnetic strap to hang the instrument on the wall while you work.
Simply touch the test leads to the battery terminals to easily capture battery condition data. Automatically save measurements results using the auto-hold or auto-memory function in just 2 seconds.
Applications
| Resistance Measurement Range | 3 mΩ (max. display 3.100 mΩ, resolution 1 μΩ) to 3 Ω (max. display 3.100 Ω, resolution 1 mΩ), 4 ranges Accuracy: ±0.8 % rdg ±6 dgt (3 mΩ range: ±1.0 % rdg ±8 dgt) Testing source frequency: 1 kHz ±30 Hz With function for avoiding noise frequency enabled: 1 kHz ±80 Hz Testing current: 160 mA (3m/30 mΩ range), 16 mA (300 mΩ range), 1.6 mA (3 Ω range) Open terminal Voltage: 5 V peak |
| Voltage Measurement Range | ±6 V (maximum display ±6.000 V, resolution: 1 mV) to ±60 V (maximum display ±60.00 V, resolution: 10 mV), 2 ranges, Accuracy: ±0.08% rdg ±6 dgt |
| Temperature Measurement Accuracy | Measurement range: 14 to 140°F (-10 to 60°C) Maximum display: 140.0°F (60.0°C) Resolution 0.1°F (0.1°C) Measurement accuracy: ±1.8°F (±1.0°C) * When using the Clip Type Lead with Temperature Sensor 9460. * When using the Temperature Probe 9451, add ±0.9°F (±0.5°C) (cable length: 59.1" [1.5 m]). * When using the Temperature Probe 9451S, add ±0.9°F (±0.5°C) (cable length: 3.94" [0.1 m]). BT3554-50 standalone accuracy with simulated input: ±0.9°F (±0.5°C) |
| Absolute Maximum Input Voltage | 60 V DC maximum (no AC input) |
| Measurement Time | 100 ms |
| Response Time | Approximately 1.6 seconds |
| Comparator | Compares measured values with set threshold values to make judgments and reports them to the user. Judgment notification method: Results are displayed as shown below (segment) and beeping tones sound When the Voltage value (high): Resistance value (low)= PASS, Resistance value (medium)= WARNING, Resistance value (high)= FAIL When the Voltage value (low): Resistance value (low)= WARNING, Resistance value (medium)= WARNING, Resistance value (high)= FAIL If the judgment result is WARNING or FAIL, the audio tone is accompanied by a red backlight. User-selectable voltage judgment method: ABS (absolute value judgment), POL (polarity judgment ) Savable settings: 200 tables |
| Memory Functionality | Operation: Save, load, and delete measurement data, Save and delete profile information, Number of data sets: 6000, Memory architecture: 500 data sets per unit (12 units) Saved data: Saved measurement data is linked to profile information. 1. Measurement data: Data can be saved, loaded, and deleted by operating the instrument. -1. Date and time -2. Resistance value, voltage value, and temperature -3. Comparator threshold value and judgment result 2. Profile information: Profile information can be saved, loaded, and deleted using a supported application (GENNECT Cross or GENNECT One). -1. Profile numbers: 1 to 100 (Data (2), (3), and (4) below are saved for each profile number) -2. Location: User-defined comment such as location of UPS -3. Device information: User-defined comment such as UPS management number -4. Battery number: 1 to 500 (start number, end number) |
| Measurement Navigator | Operation: Announces the next battery number to be measured via a screen display and audio guidance. Preparations: Profile information that's been registered with a supported application (GENNECT Cross or GENNECT One) must be transferred to the instrument. |
| Communication Interface | USB |
| Other Functions | Temperature measurement -10 to 60°C (14 to 140°), zero-adjustment, hold, auto-hold, auto-memory, auto-power-save, clock |
| Power Supply | 8 x LR6 (AA) alkaline dry battery Continuous operating time: About 8.3 hours |
| Dimensions | 7.83 x 5.20 x 2.39" (199 x 132 x 60.6 mm) (with protector) |
| Weight | 33.9 oz (960 g) (including batteries and protector) |
Click on a category to view a selection of compatible accessories with the Hioki BT3554-10 Battery Tester, 3 mΩ to 3 Ω, ±6 to ±60 V.
| Resistance Measurement Range | 3 mΩ (max. display 3.100 mΩ, resolution 1 μΩ) to 3 Ω (max. display 3.100 Ω, resolution 1 mΩ), 4 ranges Accuracy: ±0.8 % rdg ±6 dgt (3 mΩ range: ±1.0 % rdg ±8 dgt) Testing source frequency: 1 kHz ±30 Hz With function for avoiding noise frequency enabled: 1 kHz ±80 Hz Testing current: 160 mA (3m/30 mΩ range), 16 mA (300 mΩ range), 1.6 mA (3 Ω range) Open terminal Voltage: 5 V peak |
| Voltage Measurement Range | ±6 V (maximum display ±6.000 V, resolution: 1 mV) to ±60 V (maximum display ±60.00 V, resolution: 10 mV), 2 ranges, Accuracy: ±0.08% rdg ±6 dgt |
| Temperature Measurement Accuracy | Measurement range: 14 to 140°F (-10 to 60°C) Maximum display: 140.0°F (60.0°C) Resolution 0.1°F (0.1°C) Measurement accuracy: ±1.8°F (±1.0°C) * When using the Clip Type Lead with Temperature Sensor 9460. * When using the Temperature Probe 9451, add ±0.9°F (±0.5°C) (cable length: 59.1" [1.5 m]). * When using the Temperature Probe 9451S, add ±0.9°F (±0.5°C) (cable length: 3.94" [0.1 m]). BT3554-50 standalone accuracy with simulated input: ±0.9°F (±0.5°C) |
| Absolute Maximum Input Voltage | 60 V DC maximum (no AC input) |
| Measurement Time | 100 ms |
| Response Time | Approximately 1.6 seconds |
| Comparator | Compares measured values with set threshold values to make judgments and reports them to the user. Judgment notification method: Results are displayed as shown below (segment) and beeping tones sound When the Voltage value (high): Resistance value (low)= PASS, Resistance value (medium)= WARNING, Resistance value (high)= FAIL When the Voltage value (low): Resistance value (low)= WARNING, Resistance value (medium)= WARNING, Resistance value (high)= FAIL If the judgment result is WARNING or FAIL, the audio tone is accompanied by a red backlight. User-selectable voltage judgment method: ABS (absolute value judgment), POL (polarity judgment ) Savable settings: 200 tables |
| Memory Functionality | Operation: Save, load, and delete measurement data, Save and delete profile information, Number of data sets: 6000, Memory architecture: 500 data sets per unit (12 units) Saved data: Saved measurement data is linked to profile information. 1. Measurement data: Data can be saved, loaded, and deleted by operating the instrument. -1. Date and time -2. Resistance value, voltage value, and temperature -3. Comparator threshold value and judgment result 2. Profile information: Profile information can be saved, loaded, and deleted using a supported application (GENNECT Cross or GENNECT One). -1. Profile numbers: 1 to 100 (Data (2), (3), and (4) below are saved for each profile number) -2. Location: User-defined comment such as location of UPS -3. Device information: User-defined comment such as UPS management number -4. Battery number: 1 to 500 (start number, end number) |
| Measurement Navigator | Operation: Announces the next battery number to be measured via a screen display and audio guidance. Preparations: Profile information that's been registered with a supported application (GENNECT Cross or GENNECT One) must be transferred to the instrument. |
| Communication Interface | USB |
| Other Functions | Temperature measurement -10 to 60°C (14 to 140°), zero-adjustment, hold, auto-hold, auto-memory, auto-power-save, clock |
| Power Supply | 8 x LR6 (AA) alkaline dry battery Continuous operating time: About 8.3 hours |
| Dimensions | 7.83 x 5.20 x 2.39" (199 x 132 x 60.6 mm) (with protector) |
| Weight | 33.9 oz (960 g) (including batteries and protector) |